Product Categories  /  Accessories & General Information  /  Wire Size Guide
Catalog Sheet
 Wire Size Guide

The following information is provided to assist in designing proper emergency lighting systems effectively and economically by using the smallest permissible wire size for load circuits.

When remote lighting fixtures and/or exit signs are connected to emergency lighting units, circuit runs must be of sufficient size to maintain a proper operating voltage to all lamps.

The National Electrical Code limits voltage to drop to a maximum of 5% of nominal. The Wire Size Guide Catalogue Sheet is a table that lists the maximum length or wire run based on systems voltage, wire gauge and total wattage on the run.

To determine the maximum length of a wire run not listed, divide the value of the load in watts into the constant listed at the bottom of each row.

Example, the maximum wire run for #10 wire on a 12 volt system, with a 54 watt load, is 3397 รท 54 or 62 feet.